High Water Temperature Of Diesel Generator

Time: Apr 27, 2023

High Water Temperature Of Diesel Generator

High Water Temperature Of Diesel Generator

 

Failure characteristics and causes of outlet water high temperature of diesel generator.

1.Air in the water pipe.After the generator started,with the rising water temperature,Please loosen the temperature gauge connector of the outlet pipe, drain the air until the water is unblocked, and tighten the joints of the pipe.

2.Insufficient circulating water,Under high load, the temperature of thewater is too high, and the oil temperature also rises.

(1)Pump or fan speed failed

(2)Pump impeller damaged

(3)Too large gap between the pump impeller and the casing

(4)In open circulation, water level is too low,pump can not absorb water.

(5)Insufficient radiator water in closed circulation.

(6)Water pipe blocking

 

Solution

1.Raise water level, add cooling water to clean pipeline and remove dirt in cooling water.

2.In the closed cycle,the radiator surface accumulated too much dirt,affecting the heat dissipation,please remove the dirt accumulation.

3.Replace the failed thermostat.

4.Repair or replace the wrong temperature gauge.

5.There crack at the cylinder liner.And the cooling water of radiator is bubbling,please replace the cylinder liner.

 

 